2 system states and errors, 5 operation – JUMO 705001 mTRON T - Central Processing Unit Operating Manual User Manual

Page 40

Advertising
background image

5 Operation

40

5.4.2

System states and errors

The following table lists all the system states and errors that are indicated by the "Status" and
"BusError" LEDs. In most cases, further diagnostics must be performed with the setup pro-
gram.

Category

"Status"

LED

"BusError"

LED

Meaning

Diagnos-
tics with

Recommended action

Start error

Internal error (1st boot-
loader)

Internal error (2nd boot-
loader)

No firmware (2nd boot-
loader)

LED

Replace central pro-
cessing unit.

Start error/
operation

Internal error

Setup pro-
gram

Perform restart, read
out error.

After several restart
attempts with an internal
error:

replace central process-
ing unit.

Start error

Buffer battery dead (sys-
tem start only possible with
"cold" reset)

LED

Replace buffer battery.

Start error

Various errors when start-
ing the system bus (e.g. no
memory, initialization error,
error when reading the bus
configuration)

Bus configuration not avail-
able.

If the "Com1" and "Com2"
LEDs also light up red, the
input voltage is too low
(< 19 V).

Setup pro-
gram or

Web
browser

Re-transfer configura-
tion with the setup pro-
gram.

Start error

Error in topology

Bus configuration does not
correspond to the actual
state.

Target state of hardware
configurator does not cor-
respond to the actual state.

Setup pro-
gram or

Web
browser

Check that all (manda-
tory) modules are pres-
ent and correctly
connected; check LED
display of modules; if
necessary, re-transfer
configuration with the
setup program.

Advertising