6 Configuration

Actual value

Analog signal as actual value (signal to be monitored)

Inactive

No signal selected.

Module (source of the analog signal)

The analog signal must be selected in
the following field (analog selector).

Setpoint value

Analog signal as setpoint value (reference signal for AF1 to AF6)

Inactive

No signal selected.

Module (source of the analog signal)

The analog signal must be selected in
the following field (analog selector).

Acknowledgem.

Condition for acknowledgement of the output signal (self-maintaining)

OFF

No acknowledgement required (output
signal is deactivated automatically if the
alarm condition is no longer present).

If inactive

Acknowledgement only possible if alarm
condition is no longer present.

Always

Acknowledgement always possible

Acknowledg.

signal

Signal to acknowledge the output signal

Inactive

No signal selected.

Module (source of signal)

Acknowledgement by means of a signal
(high active) that must be selected in the
following field (digital selector).

Hysteresis
function

Switching differential position around the limit value

Symmetric

Switching differential is positioned with
half above and half below the limit value.

Asymmetric left

Switching differential below the limit
value (typically)

Asymmetric right

Switching differential above the limit
value (typically)

Start-up alarm
suppression

Inactive

Limit value monitoring always operates
according to its alarm function.

Active

No alarm after power on or if limit value
or setpoint value is changed

Limit value

-3.37E+38 to 0 to +3.37E+38

Admissible deviation of the actual value

Switching

differential

0 to 1 to 99999

Switching thresholds of the output signal
(difference from limit value)

Switch-on delay

0 to 65535 s

Delay time for activation of the output
signal if alarm condition is present.

Switch-off delay

0 to 65535 s

Delay time for deactivation of the output
signal if alarm condition is no longer
present.

Pulse time

0 to 65535 s

Output signal is deactivated automati-
cally after this time.

Parameter

Selection/settings

Description

?

?