6 Configuration

Alarm

To open this window, use the "Alarm" button:

Parameters

Parameter

Selection/settings

Description

Alarm type 1, 2

Inactive

Monitoring is not active.

Min. alarm

Alarm is issued if the limit value is not
met.

Max. alarm

Alarm is issued if the limit value is
exceeded.

Limit value 1, 2

-2147483648 to 0

to 2147483647

Limit value at which the alarm is issued.

Kind of alarm 1, 2 The alarm type is not set by default.

Collective alarm

Alarm is used to form the collective
alarm.

Event

Alarm results in an entry (event text) in
the event list.

Event text 1, 2

Use default text or select other text from
the list.

Text that is entered in the event list for
an alarm (for "Event" alarm type).

Switching differ-
ential

0 to 2147483647

Used to suppress constant switching
operations in the event of minor fluctua-
tions of the input signal around the limit
value.

Alarm suppress

Signal to activate the alarm suppression

Inactive

No alarm suppression

Module (source of signal)

Alarm suppression by a signal (high
active) that must be selected in the fol-
lowing field (digital selector).

Alarm delay

0 s to 32767 s

Delay time for alarm activation

?

?

?