6 Configuration

Init string

The following Init string is required for operation as a Modbus slave:

AT&FE0X3Q1&K0S0=1&D0&W0&Y0


AT&F = Load current manufacturer profile

E0 = Deactivate character echo

X3 = Deactivate dial tone detection, activate busy tone detection

Q1 = Deactivate command responses

&K0 = Deactivate data flow control

S0=1 = Auto answer after first ring

&D0 = Ignore DTR signal

&W0 = Save current configuration as profile 0

&Y0 = Use profile 0 after switch-on

Call string, hang-up string

The dialing and hang-up strings are required if the modem needs to establish a connection to
the Internet (to send e-mail via e-mail server) or a PC with process visualization software in the
event of an alarm.

Additional settings

To open this window, use the "..." button:

Alarm signal

Signal that triggers the alarm message (only for "PC visualization" alarm type)

Inactive

No alarm message

Module (source of signal)

Alarm message is triggered by a signal
(high active) that must be selected in the
following field (digital selector).

Phone no.

(None)

(ASCII; max. 24 characters)

Telephone number for establishing con-
nection to a PC with process visualiza-
tion software

(Only for "PC visualization" alarm type)

Parameter

Selection/settings

Description