7 appendix, 1 error numbers, causes & remedies, Appendix – Lenze Loader L-force Loader User Manual

Page 36: Pendix, Error numbers, causes & remedies, C 36), Number will be displayed, Is displayed, L-force loader, 7appendix

Advertising
background image

L-force Loader

Appendix

Error numbers, causes & remedies

36

DMS 4.0 EN - 07/2007

L

7

Appendix

7.1

Error numbers, causes & remedies

Error number

Cause

Remedy

0001h ...

BFFFh

The Online Help for the system bus configurator provides information about these error

numbers.

C000h

Error while opening/closing a file.

Close the program and restart it. If the

problem still occurs, check the path and the

file name of the file causing the error.

C001h

Internal program error (invalid handling).

Restart the program. If the problem still

occurs, contact the Lenze Hotline.

C100h

Error while reading the GDC parameter set

file.

Try to reload the file. If the problem still

occurs, the GDC parameter set file is not

valid. Create a new file with GDC.

Faulty GDC parameter set file:
C101h

Error in section "ParamSet".

Create a new GDC parameter set file with

GDC.

C102h

Section "ParamSet" is missing.

C103h

UserInfo cannot be read.

C104h

PDB-ID cannot be read.

C105h

Target system name cannot be read.

C106h

Variable version cannot be read.

C200h

A code specified in the parameter set file

cannot be found in the device description.

If the device description has been assigned

manually, ensure that the device description

corresponds to the parameter set file.

Faulty GDC device description:
C201h

Error in section "DefaultParamTypes".

If the device description has been created

with DDS, create a new file. If the problem

still occurs, contact the Lenze Hotline.

C202h

Section "ParamSet" is missing.

C203h

PDB cannot be read.

C204h

PDB-ID cannot be read.

C205h

Name of ParamSet cannot be read.

C206h

SWID_B cannot be read.

C207h

Name of ParamSet is unknown.