2 .11 multiple sensors – Sensaphone 400 User Manual

Page 29

Advertising
background image

Chapter 2: Installation

27

Sensor wired to

Alert Input 2

Sensor wired to

Alert Input 3

1 C

ZONES

2 C

3 C

4 C

Figure 2-7 Two Sensors Wired to Adjacent Zones

NOTE: Do not use sensors, switches, or relays that supply any voltage

or current to the Model 400. Be aware of proximity to other electrical

wires or components when placing wires that lead from the sensors to

the unit. Avoid running the wires near electrical devices that use high

voltage or current, such as motors, heavy machinery, etc. This voltage

may be inductively coupled into the sensor wiring and could result in

damage to the the Model 400’s circuitry. Try to place wires at least 6

inches from other electrical wiring or devices.

2 .11 multIple SenSorS

The Model 400 may have more than one sensor connected to the same alert

zone, as long as the normal condition for each sensor on the same alert

zone is identical (either all N.O. or all N.C.). However, only one remote

temperature sensor can be used on each zone.
When wiring several normally closed sensors on one zone, they must be

connected in series. Connect one lead from the first sensor to the num-

bered screw of the alert zone. Next, take the other lead from the first sen-

sor and connect it to one lead from the next sensor. Continue connecting

sensors end-to-end until you have connected all of your sensors. Take the

second lead from the last sensor and connect it to the common screw on

the Model 400. See Figure 2-8. Multiple N.C. sensors are typically magnetic

reed switches to monitor the security of windows and doors.

Advertising