Press enter. the model 400 responds:“okay, Press calibrate, Enter – Sensaphone 400 User Manual

Page 78

Advertising
background image

76

SENSAPHONE 400 User’s Manual

3. Press the number (1 to 4) of the selected temperature zone to be cali-

brated.

4

MAX CALLS

3

INTERCALL

TIME

1

CALL

DELAY

2

VOICE

REPS

4. Enter the number required to offset the current temperature reading so a

correct reading is obtained.
• To program a positive offset number (up to +10 degrees), enter the num-

ber on the keypad. The Model 400 recites the digits as they are pressed.

• To program a negative offset number (up to –10 degrees), first press *.

The unit responds with “negative.” Next, enter the number on the key-

pad. The unit recites the digits as they are pressed.

4

MAX CALLS

5

TEMP LIMITS

6

CALIBRATE

8

CLOCK

3

INTERCALL

TIME

7

RECOGNITION

TIME

9

LISTEN TIME

SOUND

0

ID NUMBER

POWER

1

CALL

DELAY

2

VOICE

REPS

5. Press ENTER. The Model 400 responds:“Okay.”

ENTER

PM

NOTE: If you find that your calibration offset exceeds more than + 5

or –5 degrees, other complicating factors could be affecting normal

operation of the Model 400. Call Sensaphone for technical assistance.

5 .6 .2 InterrogatIng temperature CalIbratIon
1. Press WHAT IS.

WHAT

IS

2. Press CALIBRATE.

6

CALIBRATE