Sensaphone 400 User Manual

Page 31

Advertising
background image

Chapter 2: Installation

29

2 .12 outdoor wIrIng

When wiring sensors outdoors, DO NOT allow exposed wires to run freely

in open air; under such conditions, the Model 400 is susceptible to serious

damage during a lightning storm. Depending upon the distance outdoor

wiring must travel, consideration should be given to the use of shielded

wire inside a metal conduit. Both shield and conduit should be connected

to an earth ground. This prevents stray voltage from entering the unit.

Figure 2-10. Potential Sensor Damage from Stray Electrical Noise

2 .13 dISConneCtIng the model 400 For

Storage or SeaSonal uSe .

If you plan to employ the Model 400 as a seasonal “watchdog” for a few

months during the year, you must disconnect all wires from the unit com-

pletely to avoid damage to the circuitry when the unit is not in use. If the

unit is unplugged but left in place with all the sensors still connected, the

wires act as antennae that draw in any stray “electrical noise” from such

devices as fans, blowers, microwaves, etc.
Additionally, it is important to remove the batteries, or they will discharge

until they fail.
Preserve your Model 400 during the off-season, or when not in use:

• Remove the sensor wires at the screw terminals
• Remove the batteries
• Unplug the unit and store in a safe place

Advertising