5 .9 ac power failure recognition time, Press recognition time – Sensaphone 400 User Manual

Page 80

Advertising
background image

78

SENSAPHONE 400 User’s Manual

5 .9 aC power FaIlure reCognItIon tIme

The AC Power Failure Recognition Time is the length of time that AC elec-

tric power is off before a valid alarm is recognized and dial-out begins. The

default setting is 5 minutes, 0 seconds, but is programmable from 0 seconds

to a maximum of 540 minutes.
When AC power failure occurs, and throughout the programmed

Recognition Time, the Model 400 steadily repeats the message “the power

is off” at the unit’s installation site. There is no Call Delay programming

available for AC power failure. Immediately following Recognition Time,

the Model 400 begins the dial-out process to report power failure.
To cancel the power-failure message locally at the keypad (during or after

Recognition Time) press the ALARM CANCEL key on the Model 400 key-

pad. This action also cancels the dial-out process.

5 .9 .1 programmIng power FaIlure

reCognItIon tIme

1. Press SET.

SET

2. Press RECOGNITION TIME.

7

RECOGNITION

TIME

3. Press POWER. The Model 400 responds: “Enter minutes.”

0

ID NUMBER

POWER

4. Using the number keys, enter the number of minutes. The Model 400

will recite the digits as they are pressed.

4

MAX CALLS

5

TEMP LIMITS

6

CALIBRATE

8

CLOCK

3

INTERCALL

TIME

7

RECOGNITION

TIME

9

LISTEN TIME

SOUND

0

ID NUMBER

POWER

1

CALL

DELAY

2

VOICE

REPS

5. Press ENTER. The Model 400 responds: “Enter seconds.”

ENTER

PM

Advertising