Contactor specifications (cont.) product approvals – Rockwell Automation 1502 Medium Voltage Contactor, 800A (Series D and E) User Manual

Page 12

Advertising
background image

1-8

Contactor Product Description

1502-UM051E-EN-P – June 2013

Contactor

Specifications

(cont.)

Product Approvals

• UL347

• CSA22.2 No. 14 and T.I.L. D-21

• IEC60470

• CE Mark

Table 1.B - Bulletin 1502 Medium Voltage 800 Amp Contactor Ratings (cont.)

Description

Specifications

Operational Characteristics

Electrically Held

250

Mechanical Life (Operations) x 1000 Mechanical Latch

100

Electrical Life (Operations) x 1000

250

Electrically Held

600

Switching Frequency

(Operations per hour)

Mechanical Latch

150

Opening and Closing Times (Series E)
Maximum Closing Time

120/240 VAC (milliseconds)

150

Maximum Opening Time

(without delay)

120 to 240 VAC (milliseconds)

60

Opening and Closing Times (Series D)
Maximum Closing Time (120 VAC)

50 or 60 Hz (milliseconds)

200

Maximum Opening Time

(Normal Drop Out)

50 or 60 Hz (milliseconds)

240

Maximum Opening Time

(Fast Drop Out and Mechanical Latch)

50 or 60 Hz (milliseconds)

60

Capacitor Switching (max. KVAR)

2400 V

2000

4160 V

3000

System Voltage

6900 V

4000

General

Standard Altitude Capability (meters / feet)

-1,000 to 5,000 / -3,300 to 16,500

Contactor Weight (kg / lbs)

45 / 100

Auxiliary Contact Rating

A600

Auxilairy Contacts on the Vacuum Contactor (Max.)

3 N.O. / 3 N.C.

The voltage and current ratings listed are valid up to 1,000 m (3,300 feet). Please refer to Table 1.C – Altitude Derating Chart on

page 1-8 for ratings above this altitude.

Control voltage, as measured at the input of the IntelliVAC and IntelliVAC Plus control modules.

Provided that regular maintenance is performed.

A contactor drop-out delay may be configured with the IntelliVAC and IntelliVAC Plus control modules (refer to publications

1503-UM053_-EN-P and 1503-UM054_-EN-P).

FDO = Fast Drop-Out. NDO = Normal Drop-Out.

The number of contactor auxiliary contacts depends on the contactor type. Some of the contacts are used in the typical control

schemes used.

Altitude adjustment required.