Vacuum bottle replacement, And set-up procedure – Rockwell Automation 1502 Medium Voltage Contactor, 800A (Series D and E) User Manual

Page 32

Advertising
background image

Maintenance

4-3

1502-UM051E-EN-P – June 2013

Vacuum Bottle Replacement

The following procedure shall be used to remove and replace the vacuum

and

Set-Up Procedure

bottles. This procedure can be performed with the contactor remaining in

the power cell of the controller. After this procedure has been completed, the

contactor will be set up to operate properly at 1000 m (3300 ft). Refer to the

Altitude Adjustment procedure for other altitude setting on page 4-18.

For the safety of the maintenance personnel, remove the con-

trol wiring from the contactor by disconnecting the control

wire plug before starting any disassembly of the contactor.

1. Before removing the vacuum bottles, mark the installed bottles clearly to

avoid confusing them with the replacement vacuum bottles.

2. Remove the front retaining brace and all four interphase barriers as shown in

Figure 4.1.

Interphase Barriers

Retaining Brace

Figure 4.1 – Removal of Interphase Barriers

A T T E N T I O N