Main coil replacement procedure (cont.) – Rockwell Automation 1502 Medium Voltage Contactor, 800A (Series D and E) User Manual

Page 41

Advertising
background image

4-12

Maintenance

1502-UM051E-EN-P – June 2013

3. Remove the two bolts which connect the magnet core to the core mounting

plate as shown in Figure 4.14.

4. Slide the core out of the coil as shown in Figure 4.14. If there is a tight fit,

tap the core out with a hammer.

Core

Mounting Plate

Coil Leads

Series D

Hold-in Coil

Closing Coil

Core

Mounting Plate

Coil Lead

Series E

Figure 4.14 – Magnet Assembly

5. Slide the core into the new coil with the mounting hole end located towards

the closing coil. Ensure that the coil leads are oriented properly with respect

to the core mounting holes.

6. Bolt the core to the mounting plate and position the magnet assembly in the

contactor. Install the three (3) bolts which retain the assembly and torque

all bolts to 20 ft-lb.

7. Referring to Figures 4.15 and 4.16 for Series D or Figure 4.17 for Series E

electrically held contactors, connect the leads from the coil to the terminal

block assembly as follows:

Series D:

• Closing coil (yellow lead) to “C”

• Closing coil (black lead) to “D”

• Hold-in coil (yellow lead) to “P”

• Hold-in coil (blue lead) to “N”

Series E:

• Closing coil (yellow lead) to “C”

• Closing coil (black lead) to “N”

Main Coil Replacement

Procedure (cont.)

Advertising