Rockwell Automation 1502 Medium Voltage Contactor, 800A (Series D and E) User Manual

Page 48

Advertising
background image

Maintenance

4-19

1502-UM051E-EN-P – June 2013

Table 4.A – Dimension “A” Settings in Inches (millimeters in brackets)

EXISTING

NEW ALTITUDE RANGE

ALTITUDE

Increase or Decrease Dimension “A” by:

RANGE

0-1000 m

1000-2000 m

2000-3000 m

3000-4000 m

4000-5000 m

0-1000 m

N/A

+0.073 (1.85)

+0.140 (3.56) +0.194 (4.93)

+0.246 (6.25)

1000-2000 m

-0.073 (-1.85)

N/A

+0.067 (1.70) +0.121 (3.07)

+0.173 (4.39)

2000-3000 m

-0.140 (-3.56) -0.067 (-1.70)

N/A

+0.054 (1.37)

+0.106 (2.69)

3000-4000 m

-0.194 (-4.93) -0.121 (-3.07) -0.054 (-1.37)

N/A

+0.052 (1.32)

4000-5000 m

-0.246 (-6.25) -0.173 (-4.39) -0.106 (-2.69) -0.052 (-1.32)

N/A

4. On the rating label, change the catalog number (altitude suffix), the stated

altitude range and the current rating. Refer to Table 4.B for the derated

continuous current and B.I.L. withstand ratings for each altitude range.

A contactor will only function properly in the altitude range

for which it is set up. If functional tests are required, they

must be performed at the proper altitude or in a pressure

chamber which simulates the proper altitude.

A T T E N T I O N

Table 4.B – Contactor Deratings

Altitude Range

Continuous

Current Rating

B.I.L. Withstand

Rating

0-1000 m

800 A

60 kV

1000-2000 m

780 A

54 kV

2000-3000 m

760 A

48 kV

3000-4000 m

740 A

42 kV

4000-5000 m

720 A

36 kV