Mechanical latch trip coil replacement procedure – Rockwell Automation 1502 Medium Voltage Contactor, 800A (Series D and E) User Manual

Page 44

Advertising
background image

Maintenance

4-15

1502-UM051E-EN-P – June 2013

8. The closing coil is the larger of the two (Series D only) and is located toward

the front of the contactor. Refer to the appropriate wiring diagram (Chapter

3 – Installation) to ensure that the bridge diode and/or MOV leads are

properly connected and for complete control wiring details.

9. Ensure that all leads, diodes and MOVs are secured tightly. Operate the

contactor several times to ensure that the core is located properly.

Before beginning work on the contactor, ensure that it is

isolated from all power sources and locked out, and that

the contactor is in the open (or tripped) state.

Figure 4.20 – Mechanical Latch Assembly

1. Disconnect the trip coil leads from the terminal block assembly. The trip

coil leads are the blue and white wires connected to terminals "B" and "D"

respectively (see Figure 4.18 or 4.19). Cut any wire ties fastening the leads to

the contactor base.

2. Remove latch pivot bolt with a 3/16" Allen key as shown in Figure 4.21, and

remove the lever assembly. The latch spring is no longer retained at this

point and may fall out of the core – do not misplace this spring.

3. Remove the trip core mounting bolt as shown in Figure 4.22 and slide the

core out of the coil allowing the coil to be removed.

4. Slide the core into the new coil and install the core mounting bolt.

Mechanical Latch Trip Coil

Replacement Procedure

A T T E N T I O N

Latch Lever Assembly

Yoke Plate

Latch Roller

Manual Trip Actuator

Manual Trip Guide Block

Trip Coil (core hidden)

Core Mounting Plate