Maintenance

4-23

1502-UM051E-EN-P – June 2013

Auxiliary Contact Assembly

Mounting Bolt

Cam Followers

Operating Lever

Mounting Bolt

Figure 4.28 – Auxiliary Contact Assembly Set-up

6. Connect all control wire leads to the appropriate cartridge terminals per

the appropriate electrical diagram (Chapter 3), or per the specific electrical

drawing “ED” supplied with the starter unit.

7. Operate the contactor several times to ensure proper positioning of the

auxiliary assembly as well as proper connection of the control wires.