Chapter

1

Contactor Product Description

Scope

This User Manual pertains to Allen-Bradley's Bulletin 1502, 800A vacuum

contactors. It applies to both Series D and E versions of the Bulletin 1502 (800

Amp) contactors.

Series D vacuum contactors are intended for use with electro-mechanical (relay)

control circuits. They may not be used with IntelliVAC and IntelliVAC Plus

control modules.

Series E vacuum contactors are used with IntelliVAC and IntelliVAC Plus

control only (refer to publications 1503-UM053_-EN-P and 1503-UM054_-EN-P

respectively).

Description

Allen-Bradley's Bulletin 1502, 800 amp electrically held and mechanical latch

vacuum contactors are designed for high horsepower applications in the 2400 to

7200 voltage range. These contactors are suitable for all types of AC loads, for

example: three phase motors, transformers, power capacitors and resistive

heating loads. Mechanically latched contactors are used mainly in situations

requiring the contactor to remain closed in the event of power failure.

The contactor uses three (3) interrupters (hereafter referred to as vacuum bottles)

operated by an electromagnet assembly through a mechanical linkage. They are

resistant to adverse atmospheric conditions and provide a long mechanical and

electrical life.

The contactors are utilized in various starter and drive configurations, e.g. full

voltage non-reversing, full voltage reversing, two-speed, reduced voltage, synchro-

nous, drive input/output and bypass applications. They are fixed mounted

within the structures and the line and load terminations are made at the rear of

the device. In most configurations, the main contactor is mechanically inter-

locked with the external operating handle and isolating switch.

Figure 1.1 – 800A Contactor

1502-UM051D-EN-P – December 2009