Rockwell Automation 1502 Medium Voltage Contactor, 800A (Series D and E) User Manual

Page 7

Advertising
background image

Contactor Product Description

1-3

1502-UM051E-EN-P – June 2013

Contactor Operation

The standard electrically held contactor consists of three vacuum bottles oper-

ated by an electromagnet assembly through a mechanical linkage (See Figure

1.3).

Electro-Mechanical Control (Series D)

• When the control circuit is energized, current flows through both a closing coil

and hold-in coil, creating an electromagnet.

• This electromagnet pulls the armature plate towards the coil cores which also

rotates the actuator shaft.

• The actuator plate, in turn, pushes the insulator and movable shaft up, closing

the contacts inside the vacuum bottle.

• The control circuit economizing/auxiliary contacts, located on the left side of

the contactor, change state once the contactor closes.

• The current that is energizing the closing coil is then switched off. The contac-

tor remains closed by the hold-in coil only.

• The contactor is opened by de-energizing the hold-in coil.

The mechanical latch version of the contactor operates basically the same way

with the following exceptions:

• Both coils are de-energized upon closing of the contactor, and the armature is

held in the closed position by a spring-loaded latching mechanism.

• The contactor is opened by energizing a trip coil which pulls the latch away

from the armature, or by engaging a manual trip mechanism via a pushbutton

located on the front of the medium voltage door (see Figure 1.4).

Note: External control relays and a rectification circuit are used to control the

standard DC closing and hold-in coils on the contactor.

Advertising