4-16
Maintenance
1502-UM051E-EN-P – June 2013
5. Make sure that the latch spring is seated properly in the core, position the
lever assembly and install the latch pivot bolt. The spring must be seated
properly in the retaining holes in both the core and the lever.
6. Route the trip coil leads as they were and connect to the terminal block as-
sembly as shown in Figure 4.18 or 4.19.
Latch Pivot Bolt
Lever Assembly
Latch Spring
Figure 4.21 – Mechanical Latch Trip Coil Replacement
Figure 4.22 – Mechanical Latch Trip Coil Replacement
Mechanical Latch Trip Coil
Replacement Procedure (cont.)
Latch Spring
Trip Core
Trip Coil
Trip Core Mounting Bolt