Maintenance

1502-UM051E-EN-P – June 2013

Drop-out Time Conversion

Series D

The average normal drop-out time for the contactor is 200 ms. The "fast drop-

out" contactor has a drop-out time less than 60 ms. Conversion from "normal"

to "fast" or vice-versa is easily achieved by changing the control component wired

in parallel with the closing coil (see Figures 3.3 and 3.4). The required compo-

nents can be ordered from Rockwell Automation and installed per the appropri-

ate schematic.

Normal drop-out parts:

(1) Rectifier bridge

24808-451-01

(1) Mounting screw

M-8765

(1) Wire assembly

80018-457-32

(1) Wire assembly

80018-457-33

Fast drop-out parts:

(1) MOV assembly

80145-581-03

The rectifier bridge for the normal drop-out mounts on the outside of the left

side plate above the auxiliary assembly (mounting hole provided). The MOV for

the fast drop-out mounts directly on the terminal blocks as shown in Figures

4.15 and 4.16.

Series E

Contactor drop-out times are set within and controlled by the IntelliVAC or

IntelliVAC Plus control modules (refer to publications 1503-UM053_-EN-P or

1503-UM054_-EN-P).