4-22

Maintenance

1502-UM051E-EN-P – June 2013

Top cartridges normally closed

(See Note on previous page)

Bottom cartridges normally open

Auxiliary assembly removed

Figure 4.27 – Auxiliary Contact Assembly

3. Position the new assembly on the left side plate of the contactor with the

cam followers (see Figure 4.28) protruding through the rectangular holes in

the operating lever. Install and allow the mounting bolts to remain loose so

that the assembly can slide vertically on its mounting slots.

4. With the contactor “off ”, push the entire auxiliary assembly up until the cam

followers bottom out against the top of the rectangular holes in the operat-

ing lever as shown in Figure 4.28 (make sure the armature plate is against

the stop such that the contactor is fully open). At this point, the top set of

auxiliary contacts are “closed” and the bottom set of auxiliary contacts are

“open”.

5. Tighten and torque (6 ft-lb) the mounting bolts to fix the position of the

auxiliary assembly.

Auxiliary Contact Replacement

and Set-Up Procedure (cont.)

Advertising