Rockwell Automation 1502 Medium Voltage Contactor, 800A (Series D and E) User Manual

Page 35

Advertising
background image

4-6

Maintenance

1502-UM051E-EN-P – June 2013

7. Reassemble the assembly using a new vacuum bottle, leaving the bottom gap

locking nut and lock washer off. Position the insulator to achieve the 243.3

mm (9.58 in.) dimension as shown in Figure 4.6 and leave the load terminal

nut loose (the position of the load terminal shall be in the opposite direction

of the wear indicator line on the movable shaft). Repeat this procedure for

the remaining vacuum bottle assemblies.

The 9.58" dimension is not critical, it is simply a good starting point in order

to make the installation easier.

Movable Shaft

Load Terminal

Load Terminal Nut

9.58” (243.3 mm)

Figure 4.6 – Reassembled Vacuum Bottle Assembly

8. Position a 4.76 mm (0.1875 in.) diameter rod, e.g. drill bit or screw, between

the armature plate and the yoke plate to prevent the contactor from closing

as shown in Figure 4.7.

Yoke Plate

(Position 3/16” rod here)

Armature Plate

Figure 4.7 – Set-up Position