Wiring the 1734-232asc module, Wiring the 1734-485asc module, Rs-232 – Rockwell Automation 1734-485ASC POINT I/O ASCII User Manual User Manual

Page 16

Advertising
background image

Publication 1734-UM009B-EN-P - July 2003

1-6 Installing the ASCII Module

Wiring the
1734-232ASC Module

Wiring the
1734-485ASC Module

Module

Status

Network

Status

1734

232ASC

1734

232ASC

NODE:

TxD

RxD

43123

Rx

NC

NC

SG

Tx

NC

NC

NC

Module Status

Network Status

Tx = Transmit

Rx = Receive

NC = No Connection

SG = Signal Ground

Shielded Cable: The 1734-232ASC module
requires shielded cable to help reduce the
effects of electrical noise coupling. Ground
each shield at one end only. A shield grounded
at both ends forms a ground loop, which can
cause module communications to fault. Never
connect a shield to the common side of a logic
circuit (this would introduce noise into the
logic circuit).

Connect the shield directly to a chassis ground.
This chassis ground connection is not available
on the 1734-232ASC RTB (Removable Terminal
Block). On a POINT I/O system, the chassis
ground connection can be made at the DIN
Rail, at the metal panel the DIN Rail is
mounted to, or at the user’s I/O device.

RS-232

NC

NC

NC

SG

S+

S-

NC

CG

Module

Status

Network

Status

S+ = Transmit

S- = Receive

CG = Chassis Ground

NC = No Connection

SG = Signal Ground

Shielded Cable: The 1734-485ASC module requires
shielded cable to help reduce the effects of electrical
noise coupling. Ground each shield at one end only. A
shield grounded at both ends forms a ground loop, which
can cause module communications to fault. Never connect
a shield to the common side of a logic circuit (this would
introduce noise into the logic circuit).
Connect the shield directly to a chassis ground. This
chassis ground connection is not available on the
1734-485ASC RTB (Removable Terminal Block). On a
POINT I/O system, the chassis ground connection can be
made at the DIN Rail, at the metal panel the DIN Rail is
mounted to, or at the user’s I/O device.

Rx+

Rx-

NC

SG

Tx+

Tx-

NC

CG

Tx = Transmit

Rx = Receive

CG = Chassis Ground

NC = No Connection

SG = Signal Ground

Module

Status

Network

Status

RS-485

RS-422

43487

43487

Advertising
This manual is related to the following products: