Rockwell Automation 1734-485ASC POINT I/O ASCII User Manual User Manual

Page 56

Advertising
background image

Publication 1734-UM009B-EN-P - July 2003

3-2 Diagnostics

Table 3.2 Network Status Indicators

Indication

Probable Cause

Network Status

Off

Device is not on-line.

- Device has not completed dup_MAC_id test.

- Device not powered - check module status indicator.

Flashing Green

Device is on-line but is not allocated to a master.

Green

Device on-line and has connections in the established
state.

Flashing Red

One or more I/O connections in timed-out state.

Red

Critical link failure - failed communication device. Device
detected error that prevents it communicating on the
network.

Table 3.3 Transmit/Receive Indicators

Indication

Probable Cause

Transmit/Receive Status

Flashing Transmit/
Off Receive

Check wiring, ground, and RX connection. User parameter
object to view transaction IDs.

Flashing Receive/
Off Transmit

Check wiring. Watch TX light. If it does not flash, check
that you are properly initiating transmission. Use EDS
parameter object to try transmitting and watch the light.
If it flashes, you are not properly initiating transmission
via I/O messaging. If it does flash, check the remote
device.

Off Transmit/
Green Receive

Check connections as you may have wired the device
backwards.