1-8 Installing the ASCII Module

Cable Pinouts for
Standard DB Connectors

How to Install a Serial
Network

The communication between your serial device(s) and the:

· 1734-232ASC is an RS-232 3-wire network.
· 1734-485ASC is an RS-485 2-wire network

or RS-422 4-wire network

1. Connect an appropriate cable to your device.

2. Connect the other end of the cable to the ASCII module using

the designated positions on the 1734-TB terminal block.

Notice the terminal markings on the ASCII module case.

3. Turn on power to the serial device and the ASCII module.

4. Set up the ASCII buffer sizes on the ASCII module.

The defaults are 20 and 20. If more than 20 bytes are required
for the transmit or receive buffers, set the appropriate
parameters in your configuration file to the buffer size you need
for your ASCII data.

This will modify the I/O message size. You will need to
reconfigure the poll/COS/cyclic transmit and receive data sizes if
you modify the ASCII buffer size from the default value.

In many configuration tools, this will unmap the data in your
scanner’s scan list. They must be remapped in order to process
the data in your PLC or PC software. These values are displayed
in the Parameter Object, Class 15 (F

hex

).

Table 1.1 ASCII Functions

Pin Number

Function

DB-25

DB-9

Transmit Data (TXD)

2

3

Receive Data (RXD)

3

2

Signal Ground (SG)

7

5