Specifications A-3

Specifications - 1734-232ASC, -485ASC Modules (Continued)

EFT/B Immunity

IEC 61000-4-4:
+4kV at 2.5kHz on power ports
+2kV at 5kHz on signal ports

Surge Transient Immunity

IEC 61000-4-5:
+1kV line-line(DM) and +2kV line-earth(CM) on
signal ports
+1kV line-line(DM) and +2kV line-earth(CM) on
power ports

Conducted RF Immunity

IEC 61000-4-6:
10Vrms with 1kHz sine-wave 80%AM from
150kHz to 80MHz

Emissions

CISPR 11
Group 1, Class A

Enclosure Type Rating

None (open-style)

Conductors

Wire Size

14 AWG (2.5mm

2

) - 22AWG (0.25mm

2

) solid or

stranded copper wire rated at 75

°C or greater

3/64 inch (1.2mm) insulation

Category

2

1

RS-232 Field Wiring Terminations

0 - Tx

1 - Rx

2 - NC

3 - NC

4 - NC

5 - NC

6 - NC

7 - SG

RS-485 Field Wiring Terminations

0 - S+

1 - NC

2 - S-

3 - NC

4 - NC

5 - NC

6 - CG

7 - SG

RS-422 Field Wiring Terminations

0 - Tx+

1 - Rx+

2 - Tx-

3 - Rx-

4 - NC

5 - NC

6 - CG

7 - SG

Terminal Base Screw Torque

7 pound-inches (0.6Nm) maximum

Mass

1.22 oz/34.6 grams

Agency Certification (when product is
marked)

CE

2

- European Union 89/335/EEC EMC

Directive, compliant with:
EN 50081-2; Industrial Emissions
EN 50082-2; Industrial Immunity
EN 61326; Meas./Control/Lab., Industrial
Requirements
EN 61000-6-2; Industrial Immunity
C-Tick

2

- Australian Radiocommunications Act

compliant with AS/NZS 2064, Industrial
Emissions

Installation Instructions

Publication 1734-IN588

1

Use this conductor category information for planning conductor routing as described in publication 1770-4.1,
“Industrial Automation Wiring and Grounding Guidelines.”

2

See the Product Certification link at www.ab.com for Declaration of Conformity, Certificates, and other
certification details.