Rockwell Automation 1734-485ASC POINT I/O ASCII User Manual User Manual

Page 17

Advertising
background image

Publication 1734-UM009B-EN-P - July 2003

Installing the ASCII Module 1-7

Module Terminations

Terminal

RS-232

RS-485

RS-422

0

Tx

1

S+

1

Tx+

1

1

Rx

2

NC

Rx+

1

2

NC

S-

2

Tx-

2

3

NC

NC

Rx-

2

4

NC

NC

NC

5

NC

NC

NC

6

NC

CG

CG

7

SG

SG

SC

1 S+ and Tx+ are transmit from the module

2 S- and Rx- are receive into the module

0

1

2

3

4

5

6

7

Tx

NC

NC

NC

Rx

NC

NC

SG

43124

Tx, S+ = Transmit

Rx, S- = Receive

NC = No Connection

SG = Signal Ground

CG = Chassis Ground

0

1

2

3

4

5

6

7

S+

S-

NC

CG

NC

NC

NC

SG

43488

0

1

2

3

4

5

6

7

Tx+

Tx-

NC

CG

Rx+

Rx-

NC

SG

43489

RS-422

RS-485

RS-232

Advertising