Rockwell Automation 1734-485ASC POINT I/O ASCII User Manual User Manual

Page 39

Advertising
background image

Publication 1734-UM009B-EN-P - July 2003

Configuring Your ASCII Module 2-13

Serial Port Transmit/Explicit Messages from Configuration Tool

Transmit Serial
Data String

24

Get/Set

Serial data to be
sent to the serial
transmit buffer

ASCII Block Data

0-128 bytes long

Empty

Empty

SHORT_

STRING

Transmitted Serial
Data Length

25

Get/Set

Length of the
Transmit Serial Data

0-128

0

0

USINT

Transmit transaction
ID

26

Get/Set

The transaction ID
of the current
transmit data buffer

0-255

0

0

USINT

Status

27

Get

The Combined
status byte for the
Serial Port Object,
the Receive Record
object and the
Transmit Record
object.

1 = TX FIFO Overflow
2 = RX FIFO Overflow

4 = RX Parity Error

64 = Handshake Error

128 = New Data Flag

No Status

0

USINT

POINTBus Options

Autobaud

28

Get

Autobaud allows the
module to match the
baud rate of existing
devices on a
network. Changes to
this attribute take
effect after the next
powerup. If
’Enabled’, the Baud
Rate Attribute
cannot be set.

0 = Enable

1 = Disable

Enable

1

USINT

Table 2.3 Parameter List

Parameter

Parameter

Instance

Access

Description

Parameter Choices

Default

Setting

Default

Value

Data Type