Publication 1734-UM009B-EN-P - July 2003

Configuring Your ASCII Module 2-11

Send (Produce) on DeviceNet to Master

Receive String
Data Type

8

Get/Set

Defines the format
of the data string to
the master

0 = Array

1 = Short_String

2 = String

Short_

String

1

USINT

Pad Mode

9

Get/Set

Indicates whether to
pad the invalid data
region after the
delimiter with the
pad character, or to
use variable length
I/O responses

0 = Pad Mode

Disabled

1 = Pad Mode

Enabled

Enabled

1

USINT

Pad Character

10

Get/Set

Value to use to pad
the invalid data
portion of the poll
response

Any valid standard

ASCII character

(0-127, 0-255)

NULL

0

USINT

Receive Swap Mode

11

Get/Set

If enabled, the
position of the bytes
in the serial
messages will be
swapped every 2, 3
or 4

0 = Disabled

1 = 16-bit Swap

Enabled

2 = 24-bit Swap

Enabled

3 = 32-bit Swap

Enabled

Disabled

0

USINT

Master/Slave
Handshake Mode

12

Get/Set

If enabled, master
must acknowledge it
is ready for next
new data before
1734-232ASC
module sends the
new data.

0 = Master/Slave

Handshake

1 = Produce

Immediate

Produce

Immediate

1

USINT

Produce Assembly
Size

13

Get

Total number of
bytes of I/O data
that are sent to the
master from the
1734-232ASC
module. This should
be the RX size of
your scanner.

4-132

20 bytes of

array data

and 4

header

bytes

24

USINT

Serial Data

14

Get

Serial data in the
receive buffer

Any data string

0-128 bytes long

Empty

Empty

SHORT_

STRING

Receive Data Size

15

Get

Number of
characters in the
Receive data buffer

0-128

0

0

USINT

Receive transaction
ID

16

Get/Set

The Receive
transaction ID sent
from the master

0-255

0

0

USINT

Table 2.3 Parameter List

Parameter

Parameter

Instance

Access

Description

Parameter Choices

Default

Setting

Default

Value

Data Type