Rockwell Automation 1734-485ASC POINT I/O ASCII User Manual User Manual

Page 40

Advertising
background image

Publication 1734-UM009B-EN-P - July 2003

2-14 Configuring Your ASCII Module

Sequential
AutoAddress

29

Get

Sequential
AutoAddress will
reassign the node
address of every
module to the right.
Each module will
change it’s node
address to one
greater than it’s
neighbor. Make sure
the node address of
this module is the
desired value before
issuing this
command. When the
command is set,
each module to the
right will get a new
address one greater
than it’s neighbor.

0 = Do Nothing

1 = Sequential

Address

Do Nothing

0

USINT

Broadcast Baud
Rate

30

Get

This command will
change the baud
rate of this and
every module to the
right to the value
indicated. If
AutoBaud is
ENABLED, this
command will not
change the
operation of the
module at power up.

0 = Do Nothing

1 = 125k Hz
2 = 250k Hz
3 = 500k Hz

Do Nothing

0

USINT

Broadcast AutoBaud

31

Get

This command will
change the
AutoBaud attribute
of this and every
module to the right
to the value
indicated. If
AutoBaud is
’disabled’, the Baud
Rate parameter will
set the baud rate the
next time the
module is powered
up.

0 = Do Nothing

1 = Enable

2 = Disable

Do Nothing

0

USINT

Table 2.3 Parameter List

Parameter

Parameter

Instance

Access

Description

Parameter Choices

Default
Setting

Default

Value

Data Type

Advertising
This manual is related to the following products: