About these examples, Appendix a, Appendix – Rockwell Automation 1734-485ASC POINT I/O ASCII User Manual User Manual

Page 61: Serial port connector

Advertising
background image

1

Publication 1734-UM009B-EN-P - July 2003

Appendix

B

Using the ASCII Modules with the
ControlLogix System Application Examples

About These Examples

For these application examples, the 1734-PDN POINT I/O interface
was used to interface with the DeviceNet network. The ASCII modules
act as a normal slave to the master scanner. The data that is sent
to/from the scanner contains the ASCII data and some specialty bytes.

Serial Port Connector

The ASCII devices are connected to the ASCII modules via a:

· 3-wire communications cable for the RS-232 network.
· 2-wire communications cable for the RS-485 network.
· 4-wire communications cable for the RS-422 network.

Table B.1 Module Terminations

Terminal

RS-232

RS-485

RS-422

0

Tx

1

S+

1

Tx+

1

1

Rx

2

NC

Rx+

1

2

NC

S-

2

Tx-

2

3

NC

NC

Rx-

2

4

NC

NC

NC

5

NC

NC

NC

6

NC

CG

CG

7

SG

SG

SC

1 S+ and Tx+ are transmit from the module

2 S- and Rx- are receive into the module