Configuring Your ASCII Module 2-9

Configuration Assembly

The ASCII modules support a configuration assembly, that is accessed
through the Assembly Object (Class 4), Instance 103. The
configuration assembly is 18 bytes.

Table 2.2 Configuration Assembly

Byte

Parameter

Parameter Instance
(See Table 2.3)

0

ASCII Serial Character Format

1

1

ASCII Serial Comm Speed

2

2

ASCII Max Number of Receive Characters

3

3

ASCII Receive Record Start Mode

4

4

ASCII Receive Start Delimiter

5

5

ASCII Receive Record End Mode

6

6

ASCII Receive End Delimiter

7

7

ASCII Receive String Data Type

8

8

ASCII Pad Mode

9

9

ASCII Pad Character

10

10

ASCII Receive Swap Mode

11

11

DeviceNet Handshake Mode

12

12

ASCII Max Number of Transmit Characters

17

13

ASCII Transmit End Delimiter Mode

18

14

ASCII Transmit End Delimiter Character

19

15

ASCII Consume String Data Type

20

16

ASCII Transmit Swap Mode

21

17

DeviceNet Record Header Mode

22