Operating modes, Configuration mode – Rockwell Automation 1746-HSTP1 Stepper Controller Module/ User Manual User Manual

Page 13

Advertising
background image

Publication 999-121 - December 1999

1-2 Module Overview

Differential inputs are provided for:

• Encoder Channel A and A NOT
• Encoder Channel B and B NOT
• Encoder Marker Channel

Figure 1.1 Stepper Module Overview

Operating Modes

The Module operates in three different modes: configuration,
command, and diagnostic. The three operating modes are summarized
below.

Configuration Mode

The configuration mode is commanded by setting the mode flag (bit
15 in output word 0) to 1. In this mode, the Module is configured
through the SLC Processor to perform specific operations that the user
desires. The configuration mode defines the basic operation of the
Module.

SLC
Power
Supply

Stepper

Controller

7 to 24V DC

User Power

Supply

The 24V may be obtained from the SLC Power Supply depending on application power requirements.
Motor and translator furnished by the customer.

SLC

Processor

Standard

I/O Module

Optional

Encoder

Optional Feedback Wiring

Control Wiring to Translator

Stepper

Motor

Power
Wires

Stepper

Translator

1
2

1

2

IMPORTANT

The Module does not operate until it has been
configured at least once.