Rockwell Automation 1746-HSTP1 Stepper Controller Module/ User Manual User Manual

Page 26

Advertising
background image

Publication 999-121 - December 1999

Installation and Wiring 2-9

Figure 2.8 15-volt encoder feedback connections

Notes:

1. Use 3-pair, #22 gauge individually twisted and shielded pair,

Belden 9504 or equivalent.

2. Use 1-pair, #18 gauge twisted and shielded cable.

3. Encoders must have

+5V compatible differential line drive

outputs on channels A, B, and Z. (DS8830, or equivalent.) (A-B
845H)

4.

+15V from encoder power source – connect encoder return to
0V user power (DC common) at the power supply sources.

7-24V DC user power (1)

CW + or non directional pulse output (2)

CW - or non directional pulse output (3)

CW + pulse or direction signal output (4)

CCW - pulse or direction signal output (5)

External interrupt input (6)

Home limit switch input (7)

Home Proximity limit switch input (8)

CW limit switch input (9)

CCW limit switch input (10)

Pulse train enable/disable input (11)

A Hi (Loopback + non directional pulse) (12)

A Lo (Loopback - non directional pulse) (13)

B Hi (Loopback + direction) (14)

B Lo (Loopback - direction (15)

+ Encoder Marker (16)

- Encoder Marker (17)

0 V user power (DC common) (18)

A

1

1

1

+15 VDC

Return

A

B

Z

A

H

B

I

C

J

D

F

G

Case Ground

A-B 845H

Optical

Encoder

3

Z

B

Electrical Cabinet
Ground Bus

16 AWG

16 AWG

DC

SOURCE

Advertising