Plan to Use Your Adapter

Chapter Objectives

This chapter explains how the adapter operates on a ControlNet
network and provides information to assist in configuring your
system. This chapter contains the following information.

• Overview of adapter operation

I/O connections

Rack connections

Direct connections

Explicit messaging communications

Software requirements

• Understanding ControlNet I/O

Scheduled data-transfer connections on a ControlNet network

Overview of
Adapter Operation

Connections are established between a scanner and an adapter to
exchange input and output data on the network. Status information is
transferred along with the I/O data.

I/O Connections

The adapter supports 25 direct and 5 rack I/O connections to the
POINT I/O modules. From a single 1734-ACNR adapter, multiple
controllers can establish I/O connections, up to a maximum of 5 rack
I/O connections per adapter. You must use direct connection with
analog and specialty I/O modules.

Make multiple rack connections to permit multiple controllers to
connect to I/O over a single 1734-ACNR adapter.

The number of connections that can actually be supported on a
network depends on the following.

• ControlNet parameters (NUT, RPI, API)
• POINT I/O configuration by itself (number and types of

modules)

• Type of connection to these modules (direct connection, rack

connection)