Rockwell Automation 1734-ACNR POINT I/O ControlNet Adapter User Manual User Manual

Page 68

Advertising
background image

Publication 1734-UM008B-EN-P - August 2005

A-6 1734-POINT I/O Module/RSLogix5000 Controller Tag Reference

Discrete 2 POINT Output –
With Over Load and Open
Load Diagnostic Status

1734-OB2E
2 POINT 10V-28V DC Electronically Fused Output, Source
1734-OB2EP
2 POINT 10V-28V DC Electronically Fused Protected Output, Source

Configuration Data

Data Type

Default
Value

Valid Data Values

Fault Mode - POINT 0, 1

SINT, BIT

0

0=Fault Value
1=Hold Last State

Fault Value - POINT 0, 1

SINT, BIT

0

0=Off
1=On

Program Mode - POINT 0, 1

SINT, BIT

0

0=Program Value
1=Hold Last State

Program Value - POINT 0, 1

SINT, BIT

0

0=Off
1=On

No Load Enable - POINT 0, 1
(Wire Off Diagnostic)

SINT, BIT

1

0=Disabled
1=Enabled

Auto Restart Enable - POINT 0, 1
(Over Load Behavior)

SINT, BIT

0

0=Latch Off
1=Auto Retry

Fault Latch Enable - POINT 0, 1
(Open Load or Over Load)

SINT, BIT

0

0=No Latching
1=Alarms Latch

Input Data

Data Type

Default
Value

Valid Data Values

Status Data - POINT 0, 1
(Open Load or Over Load)

SINT, BIT

0

0=Off
1=On (Load Fault)

Output Data

Data Type

Default
Value

Valid Data Values

Output Data - POINT 0, 1

SINT, BIT

0

0=Off
1=On

Advertising