1734-POINT I/O Module/RSLogix5000 Controller Tag Reference A-19

Analog 2 Channel Output

1734-OE2C
2 Channel Analog Current Output

Configuration Data

Data Type

Default
Value

Valid Data Values

Fault Value Channel 0

INT

0

-32,768 to 32,767

Program Value Channel 0

INT

0

-32,768 to 32,767

Low Engineering Channel 0

INT

1,638

-32,768 to 32,767

High Engineering Channel 0

INT

8,191

-32,768 to 32,767

Low Limit Channel 0

INT

-32,768

-32,768 to 32,767

High Limit Channel 0

INT

32,767

-32,768 to 32,767

Range Type Channel 0

SINT

0

0=4-20mA
2=0-20mA

Fault Mode Channel 0

SINT

1

0=Hold Last State
1=Go to Low Clamp
2=Go to High Clamp
3=Go to Fault Value

Idle Mode Channel 0

SINT

1

0=Hold Last State
1=Go to Low Clamp
2=Go to High Clamp
3=Go to Fault Value

Limit Alarm Latch Channel 0

SINT

0

0=No Latching
1=Alarms Latch

Alarm Disable Channel 0

SINT

0

0=Alarms Enabled
1=Alarms Disabled

Fault Value Channel 1

INT

0

-32,768 to 32,767

Program Value Channel 1

INT

0

-32,768 to 32,767

Low Engineering Channel 1

INT

1,638

-32,768 to 32,767

High Engineering Channel 1

INT

8,191

-32,768 to 32,767

Low Limit Channel 1

INT

-32,768

-32,768 to 32,767

High Limit Channel 1

INT

32,767

-32,768 to 32,767

Range Type Channel 1

SINT

0

0=4-20mA
2=0-20mA

Fault Mode Channel 1

SINT

1

0=Hold Last State
1=Go to Low Clamp
2=Go to High Clamp
3=Go to Fault Value