Rockwell Automation 1734-ACNR POINT I/O ControlNet Adapter User Manual User Manual

Page 76

Advertising
background image

Publication 1734-UM008B-EN-P - August 2005

A-14 1734-POINT I/O Module/RSLogix5000 Controller Tag Reference

1734-IR2
2 Channel RTD Input

Configuration Data

Data Type

Default Value

Valid Data Values

Low Engineering Channel 0

INT

1,000

-32,768 to 32,767

High Engineering Channel 0

INT

5,000

-32,768 to 32,767

Digital Filter Channel 0

INT

0

0 to 10,000 ms

Low Alarm Limit Channel 0

INT

-32,768

-32,768 to 32,767

High Alarm Limit Channel 0

INT

32,767

-32,768 to 32,767

Low Low Alarm Limit Channel 0

INT

-32,768

-32,768 to 32,767

High High Alarm Limit Channel 0

INT

32,767

-32,768 to 32,767

Limit Alarm Latch Channel 0

SINT

0

0=No Latching
1=Alarms Latch

Alarm Disable Channel 0

SINT

0

0=Alarms Enabled
1=Alarms Disabled

Sensor Type Channel 0

SINT

1

0=Ohms
1=100

Pt α385

2=200

Ω Pt α385

5=100

Ω JPt α3916

6=200

Ω JPt α3916

9=10

Ω Cu α427

10=120

Ω Ni α672

11=100

Ω Ni α618

12=120

Ω Ni α618

Temperature Mode Channel 0

SINT

1

0=Custom Scale
1=°C
2=°F
3=°K
4=°R

Low Engineering Channel 1

INT

1,000

-32,768 to 32,767

High Engineering Channel 1

INT

5,000

-32,768 to 32,767

Digital Filter Channel 1

INT

0

0 to 10,000 ms

Low Alarm Limit Channel 1

INT

-32,768

-32,768 to 32,767

High Alarm Limit Channel 1

INT

32,767

-32,768 to 32,767

Low Low Alarm Limit Channel 1

INT

-32,768

-32,768 to 32,767

High High Alarm Limit Channel 1

INT

32,767

-32,768 to 32,767

Limit Alarm Latch Channel 1

SINT

0

0=No Latching
1=Alarms Latch

Alarm Disable Channel 1

SINT

0

0=Alarms Enabled
1=Alarms Disabled