Publication 1734-UM008B-EN-P - August 2005

1734-POINT I/O Module/RSLogix5000 Controller Tag Reference A-3

Discrete 2 POINT Input

* POINT I/O Modules support the Unsigned Integer data type UINT
(0-65,535 range).

RSLogix5000 supports the signed Integer data type INT (-32,768 to
+32,767 range).

Filter Time Note:

To enter Filter values from +32,768 to +65,535

µs, use this conversion

formula:

Desired Filter Value (in

µs) - 65536 = Entered Filter Value (in

µs).
Example: For a 40ms filter time, 40000 - 65536 = -25536

1734-IA2
2 POINT 120V AC Input
1734-IB2
2 POINT 10V-28V DC Input, Sink
1734-IM2
2 POINT 240V AC Input
1734-IV2
2 POINT 10V-28V DC Input, Source

Configuration Data

Data
Type

Default
Value

Valid Data Values

Filter Off On Time - POINT 0

INT

1,000

-32,768 to 32,767

µs *

(0 - 65,535)

Filter On Off Time - POINT 0

INT

1,000

-32,768 to 32,767

µs *

(0 - 65,535)

Filter Off On Time - POINT 1

INT

1,000

-32,768 to 32,767

µs *

(0 - 65,535)

Filter On Off Time - POINT 1

INT

1,000

-32,768 to 32,767

µs *

(0 - 65,535)

Input Data

Data
Type

Default
Value

Valid Data Values

Input Data - POINT 0, 1

SINT, BIT

0

0=Off
1=On

Output Data

Data
Type

Default
Value

Valid Data Values

None