Add analog, digital, other, or specialty modules – Rockwell Automation 1734-ACNR POINT I/O ControlNet Adapter User Manual User Manual

Page 39

Advertising
background image

Publication 1734-UM008B-EN-P - August 2005

Configure the Adapter 4-9

Add Analog, Digital, Other,
or Specialty Modules

Select Analog, Digital, Other, or Speciality, depending on your module
type. In this example, we add a digital module.

1. Highlight the 1734-ACNR/A adapter under I/O configuration,

right-click, and select New Module .

You see the following Select Module dialog.

2. Choose + next to Digital to expand the selection, as in this dialog.

IMPORTANT

If you exceed the 1734-ACNR chassis size by trying
to add more modules than you configured, the New
Module selection is disabled and appears grayed out.
You will not be able to add any more POINT I/O
modules until you increase the 1734-ACNR chassis
size.