A-10 1734-POINT I/O Module/RSLogix5000 Controller Tag Reference

Analog 2 Channel Input

1734-IE2C
2 Channel Analog Current Input

Configuration Data

Data Type

Default
Value

Valid Data Values

Low Engineering Channel 0

INT

3,277

-32,768 to 32,767

High Engineering Channel 0

INT

16,383

-32,768 to 32,767

Digital Filter Channel 0

INT

0

0 to 10,000 ms

Low Alarm Limit Channel 0

INT

3,113

-32,768 to 32,767

High Alarm Limit Channel 0

INT

16,547

-32,768 to 32,767

Low Low Alarm Limit Channel 0

INT

2,867

-32,768 to 32,767

High High Alarm Limit Channel 0

INT

16,793

-32,768 to 32,767

Range Type Channel 0

SINT

3

3=4-20mA
8=0-20mA

Limit Alarm Latch Channel 0

SINT

0

0=No Latching
1=Alarms Latch

Alarm Disable Channel 0

SINT

0

0=Alarms Enabled
1=Alarms Disabled

Low Engineering Channel 1

INT

3,277

-32,768 to 32,767

High Engineering Channel 1

INT

16,383

-32,768 to 32,767

Digital Filter Channel 1

INT

0

0 to 10,000 ms

Low Alarm Limit Channel 1

INT

3,113

-32,768 to 32,767

High Alarm Limit Channel 1

INT

16,547

-32,768 to 32,767

Low Low Alarm Limit Channel 1

INT

2,867

-32,768 to 32,767

High High Alarm Limit Channel 1

INT

16,793

-32,768 to 32,767

Range Type Channel 1

SINT

3

3=4-20mA
8=0-20mA

Limit Alarm Latch Channel 1

SINT

0

0=No Latching
1=Alarms Latch

Alarm Disable Channel 1

SINT

0

0=Alarms Enabled
1=Alarms Disabled

Notch Filter (Channel 0 & 1)

SINT

2

1=50Hz
2=60Hz
4=250Hz
6=500Hz

Real Time Sample (Channel 0 & 1)

INT

100

0 to 10,000 ms