Currentprotection – Cyclades PM IPDU User Manual

Page 48

Advertising
background image

36

Cyclades PM IPDU Installer/Administrator/User Guide

Syntax

current [<IPDU#>|<IPDU_ID>]|reset

Arguments

<IPDU#>

IPDU number in a daisy chain

<IPDU_ID>

Identification string previously set by the id command

reset

Clears the saved peak current value

Examples

To get the current status for all units, enter the following.

To get the current status for a specific unit, enter the following.

To reset maximum current drawn, enter the following:

currentprotection

The currentprotection command turns on and off the over current protection feature. The
overcurrent protection does not let any outlet be turned on if the current drawn by the unit is greater
than the current threshold configured with the command alarm. This command may also be used to
display the current protection status. This command is available to the admin user only.

Syntax

currentprotection <on|off|status>

Arguments

on

Enables over current protection

off

Disables over current protection

status

Displays the current protection status

pm> current

IPDU #1: True RMS current: 2.2A. Maximum current: 9.4A

IPDU #2: True RMS current: 2.0A. Maximum current: 10.2A

pm> current 2

IPDU #2: True RMS current: 2.4A. Maximum current: 10.2A

pm>current reset

IPDU #1: Clearing maximum recorded current to zero.

IPDU #2: Clearing maximum recorded current to zero.