Hwocp – Cyclades PM IPDU User Manual

Page 56

Advertising
background image

44

Cyclades PM IPDU Installer/Administrator/User Guide

Arguments

<IPDU#>

IPDU number in a daisy chain

<IPDU_ID>

Identification string previously set by the id command

reset

Resets the maximum humidity registered

Examples

To get the humidity for all units in a daisy chain, enter the following.

To get the humidity for specific unit, provide the unit number as an argument, enter the following.

To reset the maximum humidity registered, use reset as a argument, enter the following.

hwocp

The hwocp command checks the status of the hardware overcurrent protection. When overcurrent
protection is on, the power is shut off. When the overcurrent protection is off or reset, the power is
on and the PM IPDU is running in normal mode. If no string identifying the IPDU is given, all PM
IPDUs in the daisy chain are affected by this command. This command is available to the admin
user only.

Syntax

hwocp [<IPDU#>|<IPDU_ID> [reset]]

Arguments

<IPDU#>

IPDU number in a daisy chain

<IPDU_ID>

Identification string previously set by the id command

reset

turn overcurrent protection off (normal operation)

pm> humidity

IPDU #1: humidity: 42.3%. Maximum: 58.7%

IPDU #2: humidity: 44.0% Maximum: 72.6%

IPDU #3: Does not have humidity sensor.

pm> humidity 2

IPDU #2: humidity: 44.0% Maximum: 72.6%

pm>humidity reset

IPDU #1: Clearing maximum recorded humidity to zero.

IPDU #2: Clearing maximum recorded humidity to zero.