Circuit Breaker Trip Time

Depending on the model, the Cyclades PM IPDU uses either one 10 amp, one 20 amp, two 15 amp,
or two 16 amp circuit breakers. The following table shows the circuit breaker trip time for all PM
IPDU models.

Table C.1: Circuit Breaker Trip Time

Current Load

Trip Time

200%

5-30 seconds

300%

1.8-10 seconds

400%

0.9-5 seconds

500%

0.5-3.3 seconds

600%

0.38-2.3 seconds

800%

0.2-1.3 seconds

1000%

0.15-0.9 seconds