Digital inputs 1 and 2 are assigned to batch start and batch run functions: BATRUN must be on (low) before the

BATSTA input starts the batch.

DIGIN1=BATSTA
DIGIN2=BATRUN
BATCHNG=MANUAL

Setpoint 1 ensures that the scale is empty (0±2

LB

).

SETPOINT=1
KIND=GROSSSP
VALUE=0
TRIP=INBAND
BANVAL=2
BATCH=ON

Setpoint 2 checks for the weight of a container (

 5

LB

) placed on the scale.

SETPOINT=2
KIND=GROSSSP
VALUE=5
TRIP=HIGHER
BATCH=ON

Setpoint 3 waits for standstill, then tares the container weight, placing the indicator in net mode.

SETPOINT=3
KIND=WAITSS
PSHTARE=ON

Setpoint 4 starts the fast fill operation. When the net weight reaches 175

LB

, the setpoint trips and digital output

1 is set off.

SETPOINT=4
KIND=NETSP
VALUE=175
TRIP=HIGHER
BATCH=ON
DIGOUT=1

Setpoint 5 controls the slow fill operation. When the net weight reaches 200

LB

, the slow fill is stopped (see

Setpoint 7), the indicator waits for standstill and performs a push print operation using the SPFMT ticket format.

SETPOINT=5
KIND=NETSP
VALUE=200
PSHPRN=WAITSS
TRIP=HIGHER
BATCH=ON
DIGOUT=2

Setpoint 6 is a continuous setpoint, used to allow the slow feed output to be on at the same time as the fast fill.

The slow fill output (digital output 2) is turned on when setpoint 4 (fast fill) starts and remains on until setpoint 5

begins.

SETPOINT=6
KIND=CONCUR
VALUE=0
START=4
END=5
DIGOUT=2