Smart Power Systems ER Series User Manual

Page 24

Advertising
background image

Smart Power

®

Systems

A. C. MODULAR GENERATOR SYSTEM

Page 23 of 52

Enabling System Purge Option

The purge option can also be set by performing the following steps:

Step 3: Hold Mode
until Amps Line 1
Blinks 88. Release
switch so 0Pt
appears.

Step 4: Press mode to
make PvrG appear.

Step 5: Press On/Off
until y appears.

Figure 10

1. If the Command & Control Center is dark, press the Mode switch to put the

display into Normal mode.

2. If the Display looks like Figure 11, The purge option is enabled.
3. Otherwise, press and hold the Mode switch until the Amps Line 1 field begins

blinking 88 (more than 10 seconds). Release the switch so 0Pt appears.
Reference Figure 10.

4. Press (and release) the Mode switch until PvrG appears.
5. Press the On/Off switch until a y appears, indicating Purge option is Active.
6. Return to system purge display by pressing the Mode switch repeatedly until the

screen shown in Figure 11 is displayed. Purge will still be active.

Indicates whether the
generator is 0n or 0ff

Example of display with purge option set

Figure 11

f. Engage the Power Take-Off (PTO). (Note: Pump may sound rough for a few

minutes due to entrapped air.) Make sure the Command & Control Center
displays the string “0FF” as shown in Figure 11, press the On/Off switch to turn
the generator off, if needed.

Advertising