Diagnostic Faults:

The following is a list of the diagnostic faults, with a brief explanation of each.

String Class

Meaning

uLu CTrL

Alarm

The control valve feedback is invalid, indicating the system is not
under control. Voltage and/or Frequency may be out of
specifications.

xI Cvrr

Alarm

Overcurrent condition. The line in which the overcurrent
condition exists is indicated by the location of the “xI” string: If in
the “Amps Line 1” field, the overcurrent is in line 1; If in the
“Amps Line 2” field, the overcurrent is in line 2.

bAd (r 1

Alarm

Current sensor fault on line 1. The indicated current may be
incorrect.

bAd (r 2

Alarm

Current sensor fault on line 2. The indicated current may be
incorrect.

bAd uoLT

Alarm

Voltage Sensor Fault. The indicated voltage may be incorrect.

xoT

<Temp>

Alarm

Oil temperature is getting too high (>175° F). Measured
Temperature in the “Hours” field

xoT <Temp>

Override

Oil Temperature is too high (>180° F). Measured Temperature
in the “Hours” field

Add 0il l0

Override

Oil level in reservoir is low. Add oil to clear the error.

xoT <Temp>

Shutdown Oil Temperature dangerous (>220° F). Measured Temperature

in the “Hours” field

bAd Ind

Alarm

Indicator Light Ground Fault. The indicator light may not
function properly.

bAd tSnS

Alarm

Temperature Sensor Fault. The indicated oil temperature may
be incorrect.

bAd Alrt

Alarm

Buzzer Ground Fault. The audible alert buzzer may not function
properly.

bAd dISP

Alarm

Display Ground Fault. The Command & Control Center may not
operate properly.

LS FAn

Alarm

Low Side Fan Short. The Fan may not operate properly

0IL FILT

Service

Warning

Service Warning: Change the Oil Filter

Table 2



Note: The fault “Classes” are defined in the table below:

Class Meaning

Service Warning

Normal maintenance needs to take place.

Alarm

A condition requires the immediate attention of the operator.

Shutdown

A condition causes the immediate shutdown of the generator.

Override

A condition that will cause the generator to be shut down in 30
minutes unless explicitly overridden by the operator.