The system controller is
configured to operate a generator
whose maximum output is this
number (in kW).

The Er indicates the system
controller is configured to
operate an ER-series
Generator

Example of configuration display

Figure 18

d. If there are no active faults, pressing the Mode switch once more will return the

Command & Control Center to its normal mode. If there are active faults, they
will be displayed in succession, one each time you press the Mode switch.

See Diagnostics in the trouble shooting section for more information on faults.


8.

If the system measures a hydraulic oil temperature that exceeds 175

F (79C), the

system will begin displaying an alarm. If the system measures a hydraulic oil
temperature that exceeds 180

F (82C), the generator will automatically shut down

in 30 minutes unless the shutdown is overridden. If the temperature of the hydraulic
oil is measured at or above 220

F, the system will immediately shut down unless

the high temperature oil warning is overridden. To override the shutdown, perform
the following steps:

Note: The system must measure a hydraulic oil temperature that exceeds 180

F for

this procedure to work.

Step a: Press Mode to
cause rvn and the y and

n labels to appear.

Step b: Press On/Off to
answer “yes” and make
the next screen appear.

Example of Command & Control Center in hot oil fault override

Figure 19