Smart Power Systems ER Series User Manual

Page 49

Advertising
background image

Smart Power

®

Systems

A. C. MODULAR GENERATOR SYSTEM

Page 48 of 52


The Pump Set option can be accessed by performing the following steps:

Step b: Hold Mode until
Amps Line 1 Blinks 88.
Release switch so 0Pt
appears.

Step c: Press mode twice
to make PSEt appear.

Step d: After selecting

PSEt, Press On/Off
until y appears.

Enabling pump set option

Figure 29


a. If the Command & Control Center is dark, press the Mode switch to put the

Command & Control Center into Normal mode.

b. Press and hold the Mode switch until the Amps Line 1 field blinks with 88 (more

than 10 seconds). Release the switch while the Amps Line 1 field is blinking to
make 0Pt appear. Reference Figure 29.

c. Press (and release) the Mode switch until PSEt appears.

d. Press the On/Off switch until a y appears, indicating Pump Set option is Active.

e. Return to Normal mode by pressing the Mode switch until the screen shown in

Figure 30 is displayed. Pump Set will still be active.

Hours field alternates
between PSET and generator
status (0n or 0ff)

Actual Generator Output
Frequency

Example of normal display with Pump Set option set

Figure 30



Advertising