Installation, Warning, Placement and clearance requirements – Steffes 5140 Owner & Installers Manual User Manual

Page 11

Advertising
background image

PlaceMent anD clearance reQuireMentS

The physical dimensions (Figure 1) of the Comfort Plus Hydronic

along with the clearances required (Figure 2) MUST be taken into

consideration when choosing its location within a structure. The

best installation location for this system is in a space requiring

heat, so some amount of the heating requirements can be satisfied

through static dissipation from the warm outer panels of the sys-

tem. Standby heat dissipation of up to 2.5kW can be experienced

in normal operation.

Room air should be maintained at less than

85° Fahrenheit.

If the Comfort Plus Hydronic is installed in an area where radiant

heat coming from the system is undesired or where room tempera-

tures may reach 85° Fahrenheit or greater, it is strongly recom-

mended to install a Static Heat Recovery unit or Air Handler.

Refer to pages 2.01-2.02 for information on these options.
In addition to the physical space requirements, the weight of the

Comfort Plus Hydronic must be taken into consideration when selecting the installation surface. A level concrete

floor is the best installation surface, but most well supported surfaces are acceptable. If unsure of floor load capac-

ity, consult a building contractor or architect.

Special requirements need to be considered if placing the system in a garage or other area where

combustible vapors may be present. Consult local, state, and national codes and regulations to en-

sure proper installation. An 18" stand (Order Item #1301585) is available to elevate the system.

rEQUIrED ClEArANCES

FIgUrE 2

installation

3

Comfort Plus Hydronic

Installation

3.02

Installation

3.01

Comfort Plus Hydronic

WARNING

Risk of fire. Can cause injury or death.

Violation of the clearance require-

ments or failure to provide proper

ventilation can cause improper

operation of the system. Main-

tain the placement and clearance

requirements as specified and

provide ventilation as necessary.

Moving the system after install

may result in equipment damage.

Do NOT move system from origi-

nal installed location.

MINIMUM ClEArANCE rEQUIrEMENTS

Back and Right Side = 3 inches (from combustible material)

Bottom = 1 inch clearance (from combustible material)

Top = 6 inches (from combustible material)

Front = 36 inches (for ease in servicing)

Left Side = 36 inches (for ease in servicing)

DIMENSIONS

FIgUrE 1

Minimum clearance requirements do NOT account for space needed for making electrical connec-

tions. If utilizing the Air Handler, additional space is required on the right hand side of the system.

Outle

t

Inlet

5140

68

5

8

"

5130

57

5

8

"

5120

46

5

8

"

29 3

16"

47 5

16"

Front View

TOP VIEW

3" REQUIRED

CLEARANCE

36" REQUIRED CLEARANCE

FRONT VIEW

6" REQUIRED CLEARANCE

36" REQUIRED

CLEARANCE

3" REQUIRED

CLEARANCE

P

M

M

A

36" REQUIRED

CLEARANCE

ELECTRIC THERMAL STORAGE

TEFFES

S

M

TEFFES

S

3" REQUIRED

CLEARANCE

1" REQUIRED

CLEARANCE