STATIC PrESSUrE

(Feet Water Column)

Based on 80 degree entry

water temperature with

a 50% glycol mix.

.1 ft @ 2 GPM

.2 ft @ 4 GPM

.4 ft @ 6 GPM

.7 ft @ 8 GPM

1.1 ft @ 10 GPM

PrESSUrE DrOP THrOUgH

HEAT ExCHANgEr

TYPICAl SYSTEM PlUMBINg

SINglE TEMPErATUrE ZONES

FIgUrE 17

TYPICAl PrIMArY lOOP

FIgUrE 16

puMp SpECIFICATIONS

Steffes recommends a Grundfos UP15-42F or equivalent single speed 115VAC pump for the primary pump.

Air Handler pump should NOT be a split phase pump.

• Air Handler pump should NOT have any type of auxiliary control built into or onto the pump.

FREEZE PROTECTION: Risk of frozen pipes. Can cause property damage. Hydronic heating system

freeze-ups WILL cause extensive damage to the entire heating system and/or property. It is the

responsibility of the installer to provide protection against freezing.
PIPING SUPPORT: Risk of exchanger damage. Can cause property damage or personal injury. DO

NOT use the exchanger as support for piping. Support brackets should be in place to ensure proper

operation of the system and to keep pressure off the inlet and outlet piping.

CAUTION

Installation

3.11

Comfort Plus Hydronic

Comfort Plus Hydronic

Installation

3.12

Air Vent

Air Separator

Inlet

Outlet

Zone

Connection

Area

Pressure

relief Valve

(Factory Supplied)

Primary loop Pump

Control Wiring

(white & red)

Junction Box

(Factory Supplied)

*Primary

loop

Pump

Expansion

Tank

Piping MUST

Be Supported

Optional

Temperature and

Pressure relief Valve

(Consult local Code)

Capacity 1.2 Gallons

Maximum Flow

10 GPM

Tubing Material

Copper

Maximum Outlet

Water Set Temperature

180°F

HEAT EXCHANGER SPECIFICATION

White

red

Primary loop

Secondary loop

Primary

loop Pump

Comfort +

Hydronic

Exchanger

This Valve Must

Be Open During

Normal Operation

White

red